What Is Thermal Runaway?

When a battery is connected to a charger, elevated temperature lowers internal resistance, allowing more current to flow. More current increases heat, which further raises temperature, repeating in a loop until the battery overheats and can fail catastrophically. In lead-acid systems, this may present as abnormal warmth, case bulging, and rapid loss of control over charge current.

In short: higher temperature → higher current → even higher temperature (a self-reinforcing loop).

Why Temperature Raises Float Current (Simple View)

In float charging, the charger maintains a small current to offset self-discharge. As temperature rises, the electrochemical kinetics accelerate and the effective float current increases, which adds thermal load. If cooling and charge control are insufficient, the loop can spiral.

Common Factors That Trigger Thermal Runaway

  1. Excessive charge voltage — Over-voltage drives higher current and heat, raising risk.
  2. Excessive charge current — Lack of current limiting overheats cells; typical practice is to cap charge current near 0.1C10 for lead-acid.
  3. High ambient temperature — Rooms above recommended range (about 20–25 °C) push float current up and reduce heat margin; cabinets also need proper ventilation.
  4. Shorted cell(s) — A failed cell can force other cells to higher per-cell voltage, increasing float current and heat.
  5. Leakage to ground — Ground faults allow large unintended currents through the battery, driving heating and runaway risk.
  6. Charger malfunction — Faulty regulation that outputs excessive voltage elevates risk.
  7. Improper installation or maintenance — Insufficient know-how, poor setup, or skipped checks increases exposure to the above issues.

Practical Prevention Checklist

Adopt the following measures to reduce the likelihood and impact of thermal runaway:

  • Use flame-retardant battery enclosures certified to standards such as UL94 and UL1778.
  • Select battery models designed to resist thermal runaway and require a passed Thermal Runaway test for the specific model.
  • Implement preventive maintenance following IEEE 1188 so issues are caught early.
  • Control environment: keep battery rooms near 25 °C and ensure good cabinet airflow.
  • Provide spacing: leave 1–2 cm between units for heat dissipation.
  • Use a charger with temperature compensation so float/equalize set-points track temperature.
  • Follow the manufacturer’s manual strictly for settings and handling.
  • Install a Battery Monitoring System (BMS/monitoring) to continuously track health and detect anomalies early.

Conclusion

Thermal runaway is preventable. By keeping voltage and current within limits, managing ambient temperature, maintaining equipment, and monitoring batteries continuously, operators can avoid the self-heating loop that leads to failure—and extend system life and safety.

All of Our Knowledges

Fallback Logo
Capacity Testing of VRLA Batteries: A Clear, Practical Guide

Capacity testing verifies whether a valve-regulated lead–acid (VRLA) battery bank can still deliver the current or power promised by its manufacturer over a specified time at a defined end-of-discharge voltage and temperature. This guide turns the technical procedure into a step-by-step checklist you can use in the field, with simple math to calculate the **Rated Capacity (%)** and account for temperature.

Fallback Logo
Thermal Runaway in Lead-Acid Batteries: Causes, Risks, and Practical Prevention

Thermal runaway is a dangerous feedback phenomenon in battery systems where rising temperature drives higher charging current, which in turn generates more heat—potentially leading to swelling, venting, or even fire.* This article explains the mechanism in plain language and distills field-ready practices to prevent it.

Lead-Acid Battery Fundamentals: How They Work, Types, and Lifespan

A complete guide to the fundamentals of lead-acid batteries. Learn about their working principles, structure, classifications (Flooded, VRLA, AGM, Gel), and the key factors like temperature and discharge that affect capacity and lifespan.

Battery Showdown: Lithium-ion vs. Advanced Lead Carbon VRLA for Stationary Applications

As the world increasingly relies on renewable energy and robust power grids, the demand for effective stationary energy storage solutions has surged. Two leading technologies dominate this space: Lithium-ion (LiB) and Advanced Lead Carbon VRLA (Valve-Regulated Lead-Acid) batteries. While Lithium-ion is known for its high performance and energy density, Advanced Lead Carbon offers a reliable and cost-effective alternative. This article provides a comprehensive comparison of these two battery types across technical specifications, safety, economics, and application suitability to help determine the best choice for various stationary uses.

Dynasty VRLA Battery System: Maintenance and Troubleshooting Guide

Valve-Regulated Lead-Acid (VRLA) batteries are widely used in backup power systems due to their sealed design and low maintenance requirements. However, to ensure reliable performance and long service life, regular inspection and systematic maintenance are essential. This guide summarizes the **periodic maintenance steps**, **troubleshooting methods**, and **best practices** for Dynasty VRLA battery systems.

Battery System Installation & Start-Up: A Clear, Practical Guide

This guide distills the uploaded “Battery System Installation and Start-Up Instructions” into a concise, field-ready article. It focuses on safety, preparation, installation sequencing, initial charging (“freshening charge”), and post-install checks for VRLA (valve-regulated lead–acid) battery systems.*

Why Lead-Acid Batteries Fail — Practical Causes, Diagnostics, and Prevention

Lead-acid batteries (flooded and VRLA/AGM/Gel) usually fail for predictable, preventable reasons. This article organizes the common failure modes, explains the electrochemistry in plain language, and outlines field diagnostics and maintenance practices to extend service life.

Fallback Logo
Choosing and Using VRLA Batteries (AGM vs. Gel): A Practical Guide

Valve Regulated Lead-Acid (VRLA) batteries are widely used in critical power systems because they’re sealed, low-maintenance, and safe when operated correctly. This guide explains how VRLA batteries work, compares Absorbent Glass Mat (AGM) and Gel technologies, and gives clear, field-ready advice for selecting the right type and operating it for long life.

Ready to Upgrade Your Power Infrastructure?

Connect with PEC Technology Today!

Secure reliable power. Minimize downtime. Future‑proof your systems.

Menu