Hero Image

Why Lead-Acid Batteries Fail — Practical Causes, Diagnostics, and Prevention

Mr. Kasiean Sukemoke

Mr. Kasiean Sukemoke

Founder & MD

August 21, 2025 at 09:59 AM# Lead-Acid Battery# Battery Failure# Battery Maintenance# Thermal Runaway# VRLA/AGM

PDF Content


PDF Summary

Lead-acid batteries (flooded and VRLA/AGM/Gel) usually fail for predictable, preventable reasons. This article organizes the common failure modes, explains the electrochemistry in plain language, and outlines field diagnostics and maintenance practices to extend service life.


Body

1.1 Overcharge

  • What it is: Float or equalize voltages set too high (often above ~2.30 V per cell at 20–25 °C) causing excess gassing and heat. VRLA cells are especially vulnerable.
  • Damage pattern: Water loss and dry-out (VRLA), accelerated positive-grid corrosion, active-material shedding, and risk of thermal runaway.
  • Field clues: Warm case on float, rising water consumption (flooded), abnormally high cell voltages, increasing ohmic values.

1.2 Undercharge

  • What it is: Float set too low, infrequent equalize, or chronic partial state of charge.
  • Core mechanism — sulfation: Hard, coarsened \(\mathrm{PbSO_4}\) crystals resist reconversion, shrinking reactive area.
  • Field clues: Low capacity despite “full” indicators, sluggish recharge, cells floating lower than peers.

Overall cell reactions (idealized):

$$ \textbf{Discharge:}\quad \mathrm{Pb} + \mathrm{PbO_2} + 2,\mathrm{H_2SO_4} \rightarrow 2,\mathrm{PbSO_4} + 2,\mathrm{H_2O} $$

$$ \textbf{Charge:}\quad 2,\mathrm{PbSO_4} + 2,\mathrm{H_2O} \rightarrow \mathrm{Pb} + \mathrm{PbO_2} + 2,\mathrm{H_2SO_4} $$


2) Plate & Grid Degradation

2.1 Positive Grid Corrosion

  • Mechanism: The positive grid slowly oxidizes, forming a thick, brittle corrosion layer that reduces conductor cross-section and can lift posts.
  • Effect: Higher internal resistance \(R_\text{int}\), hot spots, uneven charge acceptance, and capacity loss.

2.2 Loss of Active Material (LAM)

  • Mechanism: Cycling and gassing detach newly formed \(\mathrm{PbO_2}\) from the grid; shed material becomes electrically inactive.
  • Effect: Reduced available capacity and early voltage drop under rated load.

2.3 Strap/Intercell Corrosion & Post Lifting

  • Mechanism: Corroded straps or lifted posts add connection resistance and imbalance.
  • Effect: Local heating and misleading string-level readings.

3) Electrolyte & Separator Issues

3.1 Dry-Out (VRLA/AGM/Gel)

  • Causes: Chronic overcharge, high ambient temperature, or missing temperature compensation.
  • Effects: Reduced ionic pathway, rising \(R_\text{int}\), local heating, and runaway risk.

3.2 Leaks & Ground Faults

  • Causes: Case cracks, vent defects, external contamination.
  • Effects: External shunts, charge imbalance, and safety hazards.

4) Cell Faults and System Imbalance

4.1 Shorted Cell

  • Signature: One block shows abnormally low voltage while neighbors rise to absorb the charger’s total voltage; heat and gassing spike in the “healthy” cells.

4.2 Open Cell

  • Signature: One block reads abnormally high (no current sharing); string charge current collapses.

4.3 Normal vs. Abnormal Voltage Distribution

  • Healthy float: Cells cluster around \(2.25{-}2.30\ \mathrm{V/cell}\) at 20–25 °C.
  • Warning signs: Wide spreads, drifting outliers, or rapid movement relative to peers.

String voltage across \( N \) series cells:

$$ V_\text{string} = \sum_\text{i=1}^{N} V_i $$


5) Thermal Runaway

5.1 What It Is

A positive feedback loop: higher temperature increases charge current at fixed voltage, which raises \(I^2R\) (Joule) heating; drier separators (VRLA) increase \(R\), which further raises heat.

Runaway intuition:

$$ P = I^2 R, \qquad \frac{dR}{dT} > 0 ;\Rightarrow; \frac{dP}{dT} = I^2 \frac{dR}{dT} > 0 $$

5.2 Common Triggers

  • Excessive float/equalize voltage
  • Missing temperature compensation
  • High ambient temperature
  • Shorted cells or poor heat dissipation

5.3 Prevention

  • Keep float within spec (≈ \(2.25{-}2.30\ \mathrm{V/cell}\) at 20–25 °C)
  • Use temperature-compensated charging

Typical compensation slope per cell:

$$ V_\text{float}(T) \approx V_\text{float}(25^\circ\mathrm{C}) + \alpha,\big(T-25^\circ\mathrm{C}\big), \quad \alpha \approx -3~\mathrm{mV/cell/^\circ C} $$

  • Respect charge-current limits
  • Maintain ventilation and replace suspect cells early

6) Electrical Health Testing

6.1 Ohmic Testing (Conductance/Impedance/Resistance)

  • Idea: Internal elements behave like a network of resistors and capacitors; changes correlate with capacity and faults.
  • Metric: Conductance \(G\) (AC method) is often used and trends downward with degradation.

Conductance (conceptual):

$$ G = \frac{I_{\mathrm{ac}}}{V_{\mathrm{ac}}},\cos\varphi $$

  • How to use: Track each cell’s ohmic value over time; trend analysis beats single absolute thresholds. Cells trending below ~80% of the site-specific reference should be watched; below ~60% often indicates high risk.

6.2 Discharge (Capacity) Test

  • Method: Discharge with a controlled load to the specified end-voltage at the rated time (e.g., C10 to 1.80 V per cell). Log block voltages and temperatures.

Capacity calculation:

$$ %\ \mathrm{Capacity} = \frac{T_s}{T_a}\times 100 $$

where \(T_s\) is the actual discharge time and \(T_a\) is the standard/rated time.


7) Setup & Operational Best Practices

  • Float voltage: Hold within manufacturer spec (≈ \(2.25{-}2.30\ \mathrm{V/cell}\) at 20–25 °C).
  • Temperature compensation: Verify sensors and set points; a fixed float in hot rooms is a frequent root cause.
  • Equalize: Apply judiciously to counter mild sulfation; avoid chronic over-equalizing.
  • String balance: Periodically log cell/block voltages and ohmic values; act early on outliers.
  • Thermal control: Ensure airflow; avoid hot spots; watch VRLA for dry-out symptoms.
  • Charge-current limits: Many standby systems recommend \(\le 0.1,C\) to limit heating stress.

Conclusion

Lead-acid batteries rarely “just fail.” The usual culprits are incorrect float/equalize settings, heat, missing temperature compensation, and slow-creeping defects like sulfation, corrosion, dry-out, and strap/post problems. Tight voltage control, temperature-aware charging, routine voltage/ohmic trending, and periodic capacity tests catch issues early and extend service life significantly.

All of Our Knowledges

Fallback Logo
Capacity Testing of VRLA Batteries: A Clear, Practical Guide

Capacity testing verifies whether a valve-regulated lead–acid (VRLA) battery bank can still deliver the current or power promised by its manufacturer over a specified time at a defined end-of-discharge voltage and temperature. This guide turns the technical procedure into a step-by-step checklist you can use in the field, with simple math to calculate the **Rated Capacity (%)** and account for temperature.

Fallback Logo
Thermal Runaway in Lead-Acid Batteries: Causes, Risks, and Practical Prevention

Thermal runaway is a dangerous feedback phenomenon in battery systems where rising temperature drives higher charging current, which in turn generates more heat—potentially leading to swelling, venting, or even fire.* This article explains the mechanism in plain language and distills field-ready practices to prevent it.

Lead-Acid Battery Fundamentals: How They Work, Types, and Lifespan

A complete guide to the fundamentals of lead-acid batteries. Learn about their working principles, structure, classifications (Flooded, VRLA, AGM, Gel), and the key factors like temperature and discharge that affect capacity and lifespan.

Battery Showdown: Lithium-ion vs. Advanced Lead Carbon VRLA for Stationary Applications

As the world increasingly relies on renewable energy and robust power grids, the demand for effective stationary energy storage solutions has surged. Two leading technologies dominate this space: Lithium-ion (LiB) and Advanced Lead Carbon VRLA (Valve-Regulated Lead-Acid) batteries. While Lithium-ion is known for its high performance and energy density, Advanced Lead Carbon offers a reliable and cost-effective alternative. This article provides a comprehensive comparison of these two battery types across technical specifications, safety, economics, and application suitability to help determine the best choice for various stationary uses.

Dynasty VRLA Battery System: Maintenance and Troubleshooting Guide

Valve-Regulated Lead-Acid (VRLA) batteries are widely used in backup power systems due to their sealed design and low maintenance requirements. However, to ensure reliable performance and long service life, regular inspection and systematic maintenance are essential. This guide summarizes the **periodic maintenance steps**, **troubleshooting methods**, and **best practices** for Dynasty VRLA battery systems.

Battery System Installation & Start-Up: A Clear, Practical Guide

This guide distills the uploaded “Battery System Installation and Start-Up Instructions” into a concise, field-ready article. It focuses on safety, preparation, installation sequencing, initial charging (“freshening charge”), and post-install checks for VRLA (valve-regulated lead–acid) battery systems.*

Why Lead-Acid Batteries Fail — Practical Causes, Diagnostics, and Prevention

Lead-acid batteries (flooded and VRLA/AGM/Gel) usually fail for predictable, preventable reasons. This article organizes the common failure modes, explains the electrochemistry in plain language, and outlines field diagnostics and maintenance practices to extend service life.

Fallback Logo
Choosing and Using VRLA Batteries (AGM vs. Gel): A Practical Guide

Valve Regulated Lead-Acid (VRLA) batteries are widely used in critical power systems because they’re sealed, low-maintenance, and safe when operated correctly. This guide explains how VRLA batteries work, compares Absorbent Glass Mat (AGM) and Gel technologies, and gives clear, field-ready advice for selecting the right type and operating it for long life.

Ready to Upgrade Your Power Infrastructure?

Connect with PEC Technology Today!

Secure reliable power. Minimize downtime. Future‑proof your systems.

Menu